Experimental Study on Performance of a Closed Wet Cooling Tower for Air Wet-Bulb Temperature near 0°C

Experimental Study on Performance of a Closed Wet Cooling Tower for Air Wet-Bulb Temperature near 0°C

作     者:ZHOU Yasu ZHANG Pan ZHAO Jingde YANG Honghai BAI Yufeng 

作者机构:College of Environmental Science and Engineering Donghua University 

出 版 物:《Journal of Thermal Science》 (热科学学报(英文版))

年 卷 期:2019年第28卷第5期

页      面:1015-1023页

核心收录:

学科分类:08[工学] 0815[工学-水利工程] 0805[工学-材料科学与工程(可授工学、理学学位)] 0702[理学-物理学] 

主  题:closed wet cooling tower performance of cooling tower low air wet-bulb temperature rated operating parameters evaluation index 

摘      要:Closed wet cooling towers(CWCTs) are used widely because of their better water quality and smaller water consumption. However, the operating parameters shown in the technical documents are only for rated conditions in summer, not for any other conditions, especially in low air wet-bulb temperature areas such as those near 0℃. In addition, CWCTs often fail to achieve the designed cooling effect at low air wet-bulb temperatures. A experiment set of CWCT was built, and the performance of the CWCT at low air wet-bulb temperature near 0℃ was investigated. The impact of the operating parameters(air flow rate, cooling water flow rate, and spray water flow rate) on the heat and mass transfer performance of the CWCT was measured and analyzed. The results show the cooling performance of the CWCT at an air wet-bulb temperature 0℃, 2℃, and 4℃ is about 47%–63% of the rated operating condition;the optimal operating parameters of these conditions for the CWCT are just the same as those of the rated operating condition in summer. According to the experimental results, some operating advices are given.

读者评论 与其他读者分享你的观点

用户名:未登录
我的评分