Analysis of Cooling Characteristics in Datacenter Using Outdoor Air Cooling
Analysis of Cooling Characteristics in Datacenter Using Outdoor Air Cooling作者机构:Graduate School of Engineering Hokkaido University Sapporo 060-8628 Japan Faculty of Engineering Hokkaido University Sapporo 060-8628 Japan Department of Facilities Design Taisei Corporation Tokyo 163-0606 Japan
出 版 物:《Journal of Energy and Power Engineering》 (能源与动力工程(美国大卫英文))
年 卷 期:2015年第9卷第1期
页 面:16-24页
学科分类:12[管理学] 1201[管理学-管理科学与工程(可授管理学、工学学位)] 08[工学] 0805[工学-材料科学与工程(可授工学、理学学位)] 080502[工学-材料学] 081201[工学-计算机系统结构] 0812[工学-计算机科学与技术(可授工学、理学学位)]
主 题:Data center cooling characteristics outdoor air cooling PUE.
摘 要:Advancement of the information society has proceeded with the development of information and communication technology, and a demand on a data center has increased. In such a situation, the number of servers is increasing in a data center. Thus, the heat density in a data center is much higher than that of usual offices. And typically, almost 40% of the total power consumption is used for cooling servers in a data center. Thus, cooling effectiveness is one of the most important factors in evaluating the value of the data center. The data center taken up in this paper is located in Ishikari, where is a cold district in Japan. Using the cool outdoor air for cooling servers helps us to cut the power consumption for cooling. This paper first assesses the efficiency of Ishikari data center measuring the temperature of seven parts in a building where the cooling air flowing. Second, this paper describes the most efficient method for the operation and estimates 1.11 of PUE (power usage effectiveness).