Effect of inverted T arrangement on AC pollution flashover characteristics of insulator strings
作者机构:State Key Laboratory of Power Transmission Equipment and System Security and New TechnologyCollege of Electrical EngineeringChongqing UniversityShapingba DistrictChongqing400044People's Republic of China
出 版 物:《High Voltage》 (高电压(英文))
年 卷 期:2019年第4卷第2期
页 面:97-104页
核心收录:
学科分类:080801[工学-电机与电器] 0808[工学-电气工程] 08[工学] 0805[工学-材料科学与工程(可授工学、理学学位)] 080502[工学-材料学]
基 金:the National Natural Science Foundation of China(grant no.51637002)
主 题:arrangement string pollution
摘 要:The arrangement of insulator strings has an effect on its pollution flashover characteristics.A new arrangement of insulator strings,inverted T-type arrangement,is proposed in this *** electric field distribution is simulated and the pollution flashover characteristics are tested in an artificial climate *** test results indicate that the inverted T-type arrangement can greatly improve the flashover voltage of polluted insulator strings,the‘7+2’inverted T-type arrangement can increase the flashover voltage of each insulator by 8.5%on average,and the‘3+3’inverted T-type arrangement can increase the flashover voltage of each insulator by 13.4%.The discharge process is different from that of the normal suspension string when the insulator string is inverted T-shaped,i.e.a local arc is produced at the low voltage end of the insulator string and develops downward along the suspension *** as for the horizontal tension string parts,it is difficult to generate arc during discharge development.