Monitoring actual performance of ground source heat pump system using GPRS-based data transmission: A case analysis in Tangshan

Monitoring actual performance of ground source heat pump system using GPRS-based data transmission: A case analysis in Tangshan

作     者:杜红普 孔祥飞 李敏 齐承英 DU Hong-pu;KONG Xiang-fei;LI Min;QI Cheng-ying

作者机构:School of Energy and Environment Engineering Hebei University of Technology School of Civil Engineering Hebei University of Technology 

出 版 物:《Journal of Central South University》 (中南大学学报(英文版))

年 卷 期:2015年第22卷第4期

页      面:1554-1562页

核心收录:

学科分类:08[工学] 081404[工学-供热、供燃气、通风及空调工程] 0814[工学-土木工程] 

基  金:Project(2012BAJ06B04)supported by"12th Five-Year Plan"National science and Technology,China Project(2014-228)supported by Department of Housing and Urban Rural Development of Hebei,China 

主  题:ground source heat pump monitoring operation performance 

摘      要:The energy efficiency monitoring is an essential precondition for ground source heat pump system s controlling and energy saving operation. Based on the data monitoring applied in the school building, this work is focused on the parameters acquisition and operation analysis of the GSHP system in Tangshan. Results show the average COPs(coefficient of performance) are2.85 and 2.70 in summer and winter, respectively, and heat(cold) unbalance underground existed after whole year operation. The analysis of data also indicates that the direct borehole air-conditioning saved some power consumption obviously in the early stage of summer and energy saving of the GSHP system depended remarkably on its operation and management level. Besides the observation points of ground temperature are laid for a large-scale GSHP system, and the hydraulic balance of the pipes group needs to be concerned specially in safeguarding better reliability.