Identification of slot discharges in rotating machine insulation system using variable frequency PD measurement
作者机构:Cables and Diagnostics DivisionCentral Power Research InstituteBengaluruIndia Dr.Ambedkar Institute of TechnologyBengaluruIndia
出 版 物:《High Voltage》 (高电压(英文))
年 卷 期:2018年第3卷第3期
页 面:179-186页
核心收录:
学科分类:08[工学] 080502[工学-材料学] 0805[工学-材料科学与工程(可授工学、理学学位)]
基 金:Central Power Research Institute
主 题:steel rotating insulation
摘 要:Slot discharge studies are very important from the insulation diagnosis *** in practice,testing of rotating machines with power frequency requires sources which are quite bulky and *** if the diagnosis is carried out at lower frequencies(50 Hz),the size and cost of the test source can be reduced ***,it is important to know whether the study at low frequencies can be considered equivalent to study at power ***,in this study,a slot discharge phenomenon occurring in a rotating machine insulation system was investigated experimentally at different frequencies(50,10,1 and 0.1 Hz).Slot discharges are known to have a distinct phase resolved partial discharge pattern for power frequency(50/60 Hz)*** distinct patterns are useful in identifying the presence of slot discharge activity in rotating *** discharges were created on a 6.6 kV mica-epoxy stator coil and the slot discharge characteristics measured at different frequencies are *** discharge measurements were repeated by varying the air gap between the insulation surface and grounded steel *** changes in slot discharge characteristics due to the increase in air gap were found similar at all *** comparison suggests that the identification of slot discharge is also possible from the partial discharge(PD)measurement at low frequencies.