Recommended Concentration Limits of Typical Indoor Air Contaminants
Recommended Concentration Limits of Typical Indoor Air Contaminants作者机构:School of Municipal and Environmental Engineering Harbin Institute of Technology Harbin 150090 China Architectural Design and Research Institute Harbin Institute of Technology Harbin 150090 China
出 版 物:《湖南大学学报(自然科学版)》 (Journal of Hunan University:Natural Sciences)
年 卷 期:2009年第36卷第S1期
页 面:60-65页
核心收录:
学科分类:080705[工学-制冷及低温工程] 07[理学] 08[工学] 070602[理学-大气物理学与大气环境] 0807[工学-动力工程及工程热物理] 0706[理学-大气科学]
主 题:indoor air quality(IAQ) typical contaminants recommended limits(RL) evaluation method of logarithmic index percentage of dissatisfaction(PD)
摘 要:From the view of both objective and subjective factors,the indoor air quality(IAQ)evaluation was *** dioxide(CO2)and formaldehyde(HCHO)were selected as the typical contaminants of indoor air,and the evaluation method of logarithmic index was adopted as the evaluation means of *** the recommended limits(RL)of typical contaminants CO2 and HCHO were given through analysis and *** limits of CO2 and HCHO in Indoor Air Quality Standard of China or other existing standards probably correspond to the level of PD=25(%).The result shows that the existing standards fail to meet the requirement of the definition of acceptable indoor air quality,that is to say,less than 20% of the people express *** PD=20%,RL of CO2 and HCHO are 728×10-6 and 0.068×10-6 respectively,which are stricter than the limits in the existing *** method proposed in this paper is applicable to 13.1%≤PD≤86.7%.