Analyses on an electronic voltage transformer's failure by its resonance with very fast transient overvoltage and suppression

作     者:Ruoyu Han Houda Zhu Qing Chen Hongbin Li Yue Tong Linshan Han Yang Jiao 

作者机构:School of Electrical and Electronic EngineeringHuazhong University of Science and TechnologyWuhanChina China Electric Power Research InstituteWuhanChina School of Artificial Intelligence and AutomationHuazhong University of Science and TechnologyWuhanChina 

出 版 物:《High Voltage》 (高电压(英文))

年 卷 期:2024年第9卷第1期

页      面:150-162页

核心收录:

学科分类:080801[工学-电机与电器] 0808[工学-电气工程] 08[工学] 0837[工学-安全科学与工程] 0703[理学-化学] 

基  金:National Natural Science Foundation of China Grant/Award Number:U1866201 

主  题:transient resonance mentioned 

摘      要:As voltage measuring devices are widely used in the high voltage power system with a primary-secondary-fusion structure,electronic voltage transformers are directly connected to the primary conductor and would face much more serious electromagnetic environments than general secondary *** a result,they would still experience failures even when general protection measures are adopted to suppress overvoltages *** address this issue,an innovative method is proposed after analyses are conducted on the resonance between a transformer and an *** this method,an air-cored coil is installed in a transformer to artificially shift its natural frequency and to dodge the high-frequency dominant component of a transient overvoltage,avoiding the aforementioned resonance and suppressing the secondary *** addition,simulations and laboratory tests are conducted to prove this method s validity.

读者评论 与其他读者分享你的观点

用户名:未登录
我的评分