The Use of Single-Phase Immersion Cooling by Using Two Types of Dielectric Fluid for Data Center Energy Savings
作者机构:Energy and Society LaboratoryMechanical Engineering EducationUniversitas Sebelas MaretSurakarta57126Indonesia
出 版 物:《Energy Engineering》 (能源工程(英文))
年 卷 期:2022年第119卷第1期
页 面:275-286页
核心收录:
学科分类:08[工学] 080502[工学-材料学] 0805[工学-材料科学与工程(可授工学、理学学位)]
主 题:Single-phase immersion cooling data center dielectric fluid mineral oil virgin coconut oil
摘 要:Data centers are recognized as one of the most important aspects of the fourth industrial revolution since conventional data centers are inefficient and have dependency on high energy consumption,in which the cooling is responsible for 40%of the ***,this research proposes the immersion cooling method to solving the high energy consumption of data centers by cooling its component using two types of dielectric *** stages of experimentalmethods are used,such as fluid types,cooling effectiveness,optimization,and ***,benchmark software is used to measure the CPU maximum work with the temperature data performed for 24 *** results of this study show that the immersion cooling reduces 13℃ lower temperature than the conventional cooling method which means it saves more energy consumption in the data *** most optimum variable used to decrease the temperature is 1.5 lpm of flow rate and 800 rpm of fan ***,the cooling performance of the dielectric fluids shows that the mineral oil(MO)is better than the virgin coconut oil(VCO).In durability experiment,there are no components damage after five months immersed in the fluid.