咨询与建议

看过本文的还看了

相关文献

该作者的其他文献

文献详情 >Voltage Profile of Feeder with... 收藏
Voltage Profile of Feeder with Multiple Distributed Generato...

Voltage Profile of Feeder with Multiple Distributed Generators

作     者:LI Zhong-xu,SUN Qiu-ye,XU Li-li (School of Information Science and Engineering,Northeastern University, Shenyang 110004,China) 

会议名称:《2009年中国智能自动化会议》

会议日期:2009年

学科分类:080801[工学-电机与电器] 0808[工学-电气工程] 08[工学] 

关 键 词:Distributed Generation Voltage Profile Multiple DGs, Normal Curve Load Distribution Model 

摘      要:Confronted with the aging and stressful power system,a new kind of meshed and intenigent network calledIntelliGridorSmart Gridis put forward,which is regarded as the future mode of power *** Generation(DG) plays an important role in the design and realization of the futuristic IntelliGrid,due to its improvement to the power quality,reliability,and flexibility of the ***,the integration of DG in distribution networks may create technical and safety *** profile of feeder with DG connected is a key factor of power quality and an important issue in the futuristic IntelliGrid,which is focused in this ***,a normal curve load distribution model is *** based on this model,the normal curve is divided into many differential *** calculating the power loss in each differential element,the power distribution of the feeder is *** the voltage drop and voltage profile can be derived out *** simulation,the impact of DG’s number,location and capacity on voltage profile is *** shows that to ensure the feeder voltage within the permitted range,there should be some restrictions to DG’s planning scheme.