A New Method of Fault Location for 35KV Distribution Network...

A New Method of Fault Location for 35KV Distribution Network Based on The Equivalent Load to Ground

作     者:Tian Shu,Wang Xiaowei,Wang Juanjuan 

会议名称:《2011 Chinese Control and Decision Conference(CCDC)》

会议日期:2011年

学科分类:080802[工学-电力系统及其自动化] 0808[工学-电气工程] 08[工学] 

关 键 词:-fault location load earthing transient power main station 

摘      要:It installed the monitoring devices with a certain distance in the 35KV line to determine accurately the fault location in this paper,the load units were grounded with taking into account the actual operating conditions of load by the ATP *** found that the transient power waveforms of healthy section were very similar in the same side of fault point by the simulation,while the similarity of fault section was poor in the both sides of fault *** the correlation coefficient was introduced to evaluate the relationship,when the similarity is high,the value of correlation coefficient is larger,on the contrary,the value of correlation coefficient is smaller when the similarity is ***,it can compare the value calculated with the threshold value preset of main station to determine accurately the fault *** principle of this method is simple,and the data uploaded is small,so it is convenient to determine quickly the fault location.