Outage Detection for Distribution Networks Using Limited Number of Power Flow Measurements
Outage Detection for Distribution Networks Using Limited Number of Power Flow Measurements作者机构:the Department of Electrical and Computer EngineeringLehigh UniversityBethlehemPA18015USA the School of Electrical EngineeringXi'an Jiaotong UniversityXi'an 710049 the Department of Electrical and Computer EngineeringCarnegie Mellon UniversityPittsburgh.PA15213USA Lawrence Livermore National LaboratoryLivermoreCA94550USA
出 版 物:《Journal of Modern Power Systems and Clean Energy》 (现代电力系统与清洁能源学报(英文))
年 卷 期:2020年第8卷第2期
页 面:315-324页
核心收录:
学科分类:0830[工学-环境科学与工程(可授工学、理学、农学学位)] 0808[工学-电气工程] 080802[工学-电力系统及其自动化] 08[工学] 0807[工学-动力工程及工程热物理]
基 金:supported by the U.S.Department of Energy(No.DEOE0000779) the U.S.Department of Energy Grid Modernization Laboratory Consortium(GMLC)
主 题:Outage detection distribution networks maximum likelihood(ML)detection sensor placement
摘 要:Accurate topology estimation is crucial for effectively operating modern distribution *** outages in a distribution network change the network topology by disconnecting some parts of the network from the main *** this paper,an outage detection(or topology estimation)algorithm for radial distribution networks is *** algorithm utilizes noisy power flow measurements collected from a subset of lines in the network,and statistical information characterizing errors in forecasting load ***,a sensor placement scheme is *** sensor placement provides critical sensing for the outage detection algorithm so that any number of possible outages in the network can be *** performance of the proposed outage detection algorithm using the proposed sensor placement is demonstrated through several numerical results on the IEEE 123-node test feeder.