Experimental Verification to Estimate Ground Thermal Conductivity Using Spiral Coil Type Ground Heat Exchangers
Experimental Verification to Estimate Ground Thermal Conductivity Using Spiral Coil Type Ground Heat Exchangers作者机构:Department of Civil and Environmental Engineering Korean Advanced Institute of Science and Technology (KA1ST) Daejeon305-701 South Korea
出 版 物:《Journal of Civil Engineering and Architecture》 (土木工程与建筑(英文版))
年 卷 期:2014年第8卷第4期
页 面:425-429页
学科分类:080701[工学-工程热物理] 080702[工学-热能工程] 08[工学] 0807[工学-动力工程及工程热物理]
主 题:Ground thermal conductivity ground heat exchanger thermal response test spiral coil.
摘 要:This paper presents an experimental study on the evaluation of thermal response of a spiral coil type GHE (ground heat exchanger). This GHE was installed on partially saturated landfill ground that was composed of silt and clay in the runway area of Incheon International airport. TRT (thermal response test) was conducted for more than 65 hours under continuous operation conditions. Ground thermal conductivity was derived based on line source theory, which has usually been found to be appropriate for line type GHEs such as U, W and 2U types. A reasonable method to derive ground thermal conductivity using the infinite line source theory for a spiral coil type GHE was introduced. Ground thermal conductivity from the TRT using spiral coil type GHE was compared with those from the analytical equivalent model of ground thermal conductivity.