Optimization Analysis of High Temperature Heat Pump Coupling to Desiccant Wheel Air Conditioning System

Optimization Analysis of High Temperature Heat Pump Coupling to Desiccant Wheel Air Conditioning System

作     者:盛颖 张于峰 房磊 聂金哲 马丽筠 

作者机构:School of Environmental Science and Engineering Tianjin University International Centre for Indoor Environment and Energy Technical University of Denmark 

出 版 物:《Transactions of Tianjin University》 (天津大学学报(英文版))

年 卷 期:2014年第20卷第3期

页      面:182-188页

核心收录:

学科分类:080705[工学-制冷及低温工程] 08[工学] 0807[工学-动力工程及工程热物理] 

基  金:Supported by the Danish International DSF Project(No.09-71598) Chinese International Collaboration Project(No.2010DFA62410) 

主  题:desiccant wheel dehumidification adiabatic effectiveness performance optimization 

摘      要:The high temperature heat pump and desiccant wheel(HTHP&DW) system can make full use of heat released from the condenser of heat pump for DW regeneration without additional heat. In this study, DW operation in the HTHP&DW system was investigated experimentally, and the optimization analysis of HTHP&DW system was carried out. The performance of DW had influence on the dehumidification(evaluated by dehumidification and regeneration effectiveness) and cooling load(evaluated by thermal and adiabatic effectiveness). The results show that the enthalpy increase occurred in all the experiments. Compared to the isosteric heat, heat accumulation in the desiccant and matrix material and heat leakage from regeneration side to process side have greater influence on the adiabatic effectiveness. Higher regeneration temperature leads to lower adiabatic effectiveness that increases more cooling load of the system. When the regeneration temperature is 63℃, the maximal dehumidification effectiveness is 35.4% and the satisfied adiabatic effectiveness is 88%, which contributes to the optimal balance between dehumidification and cooling.

读者评论 与其他读者分享你的观点

用户名:未登录
我的评分