Hybrid Dissolved Gas-in-Oil Analysis Methods
混合溶解气体油包分析方法作者机构:Transmission System OperatorTiranaAlbania Electric Engineering FacultyPolytechnic University of TiranaTiranaAlbania
出 版 物:《Journal of Power and Energy Engineering》 (电力能源(英文))
年 卷 期:2015年第3卷第6期
页 面:10-19页
学科分类:1002[医学-临床医学] 100214[医学-肿瘤学] 10[医学]
主 题:Dissolved Gas Analysis Key Gas Methods Rogers’Ratios Transformer
摘 要:Dissolved gas analysis is the most widely used diagnostic test in power transformers. The aim of this paper is to introduce the dissolved gas analysis (DGA) methods able to diagnose the transformer conditions. The faults cause the transformer oil, pressboard, and other insulating materials to decompose and generate gases, some of which dissolve in the oil. The results of DGA must be accurate if faults are to be diagnosed reliably. There are different established methods used in industry for interpreting DGA results. We will compare the result of IEEE Key Gas Methods and Rogers’ Ratios. The transformer conditions are evaluated by the Key Gas Method with total combustible gas method (TCGM) and then verified by the Rogers’ Ratios. As result, the aging pattern and trend of the power transformer deterioration can be determined. The 30 sample data from IEEE with known faults and dissolved gas concentrations were used as the basis of comparison.