Analysis of Commutation Failure in Multi-Infeed HVDC System under Different Load Models

Analysis of Commutation Failure in Multi-Infeed HVDC System under Different Load Models

作     者:Chengjun Xia Zhongchao Yang Kun Men Yong Zhao 

作者机构:School of Electric Power South China University of Technology Guangzhou China Electric Power Research Institute of CSG China Southern Power Grid Guangzhou China 

出 版 物:《Journal of Power and Energy Engineering》 (电力能源(英文))

年 卷 期:2014年第2卷第9期

页      面:154-161页

学科分类:080802[工学-电力系统及其自动化] 0808[工学-电气工程] 08[工学] 

主  题:AC/DC Hybrid System Commutation Failure Voltage of Converter Bus Load Model Power System Simulation 

摘      要:HVDC technology has been widely used in modern power system. On one hand, HVDC has the advantages of economy, high efficiency and strong controllability. While on the other hand, it makes the dynamic characteristics of the power system becoming more and more complex. That puts forward a new challenge to system stability and raises new questions for power system simulation. This paper focuses on the interaction between AC and DC systems, especially the problem of commutation failure caused by AC system fault. Based on the data of China Southern Power Grid, this paper calculates the fault regions that may cause commutation failure and calculates the system critical clearance time under different load models, analyzes the impacts of different load models on commutation failure and the stability of AC/DC hybrid system.