Analysis and discussion of a dead-zone protection mal-operation case in Brazil
作者机构:NARI Technology Co.LTDNanjing 210003China State Grid Brazil Holding S.A.Rio de Janeiro 20071-004Brazil
出 版 物:《Journal of Modern Power Systems and Clean Energy》 (现代电力系统与清洁能源学报(英文))
年 卷 期:2014年第2卷第1期
页 面:87-91页
核心收录:
学科分类:08[工学] 0812[工学-计算机科学与技术(可授工学、理学学位)]
主 题:Brazilian power system Power system Relay protection device Dead-zone protection
摘 要:A mal-operation case of busbar protection caused by a dead-zone protection abnormality in the Brazilian Midwest Grid on September 19th,2012,is briefly *** operation process of pilot distance,automatic re-closure,busbar differential and dead-zone protection,and the emphasis on the logic scheme of dead-zone protection are *** time delay between the breaker’s main pole and auxiliary contact during re-closure was the main cause in this case,and a defect in the logic allowed it to *** differences in dead-zone protection logic between Brazil and China are discussed.A test platform was constructed in the laboratory,and a site simulated experiment was also *** causes are suggested and test activities are carried out to verify *** show the values of practical engineering approaches to the *** also contributed to avoiding future mal-operations and strengthening the reliability of the protection system,and thus of the power supply in Brazil.