文献详情 >一种现代自动控制系统设计并应用于活性污泥法废水处理过程(英文... 收藏

一种现代自动控制系统设计并应用于活性污泥法废水处理过程(英文)

Design of a modern automatic control system for the activated sludge process in wastewater treatment

作     者:Alexandros D.Kotzapetros Panayotis A.Paraskevas Athanasios S.Stasinakis 

作者机构:Water and Air Quality LaboratoryDepartment of EnvironmentUniversity of the AegeanUniversity Hill 

出 版 物:《Chinese Journal of Chemical Engineering》 (中国化学工程学报(英文版))

年 卷 期:2015年第23卷第8期

页      面:1340-1349页

核心收录:

学科分类:0710[理学-生物学] 083002[工学-环境工程] 0830[工学-环境科学与工程(可授工学、理学、农学学位)] 08[工学] 0817[工学-化学工程与技术] 0703[理学-化学] 

主  题:自动控制系统 控制系统设计 活性污泥法 污水处理 现代化 抗干扰能力 PI控制器 调整时间 

摘      要:The Activated Sludge Process(ASP) exhibits highly nonlinear properties. The design of an automatic control system that is robust against disturbance of inlet wastewater flow rate and has short process settling times is a challenging matter. The proposed control method is an I-P modi fied controller automatic control system with state variable feedback and control canonical form simulation diagram for the process. A more stable response is achieved with this type of modern control. Settling times of 0.48 days are achieved for the concentration of microorganisms,(reference value step increase of 50 mg·L-1) and 0.01 days for the concentration of oxygen(reference value step increase of 0.1 mg·L-1). Fluctuations of concentrations of oxygen and microorganisms after an inlet disturbance of5 × 103m3·d-1are small. Changes in the reference values of oxygen and microorganisms(increases by 10%, 20% and 30%) show satisfactory response of the system in all cases. Changes in the value of inlet wastewater flow rate disturbance(increases by 10%, 25%, 50% and 100%) are stabilized by the control system in short time. Maximum percent overshoot is also taken in consideration in all cases and the largest value is 25% which is acceptable. The proposed method with I-P controller is better for disturbance rejection and process settling times compared to the same method using PI controller. This method can substitute optimal control systems in ASP.

读者评论 与其他读者分享你的观点

用户名:未登录
我的评分