An investigation on topologies of hybrid manifold,impinging-jet nozzle and micro-pin-fin heat sinks

作     者:SHI QianLei YAO XiaoLe LIU Qian QIN Le JU Xing XU Chao 

作者机构:Key Laboratory of Power Station Energy Transfer Conversion and System of MOENorth China Electric Power UniversityBeijing 102206China 

出 版 物:《Science China(Technological Sciences)》 (中国科学(技术科学英文版))

年 卷 期:2024年第67卷第4期

页      面:1061-1076页

核心收录:

学科分类:080702[工学-热能工程] 08[工学] 0807[工学-动力工程及工程热物理] 0805[工学-材料科学与工程(可授工学、理学学位)] 

基  金:supported by the National Natural Science Foundation of China(Grant No.51876062) the Interdisciplinary Innovation Program of North China Electric Power University 

主  题:heat sink ultra-high heat flux manifold micro-pin-fin impinging-jet topology 

摘      要:The hybrid manifold micro-pin-fin(MMPF)heat sink combined nozzle jets is an option for large-scale integrated circuits(LSI).The demond for uniform and ultra-high heat flux removal by MMPF heat sink has not been adequately *** work aims to solve the problem of fluid *** proposed basic tiling topologies,including square,regular hexagon,30°rhombus,and 60°rhombus topologies,provide different organized fluid flows and heat transfer *** present study focuses on comparing these topologies according to independent porous medium parameters,such as nozzle pore size D_(Z),flow pore size D_(X,Y),and porosityε.The results show that the square topology achieves the smallest total thermal resistance R_(tot)value of0.0975×10^(-4)K m^2/W,while the hexagon topology achieved the highest value of COP/?T,which was 2033.9 K^(-1).According to the sensitivity analysis results,the optimal total thermal resistance can be obtained by balancing the influences of nozzle pore size,flow pore size,and *** optimal pressure drop can be obtained by maximizing the porosity.

读者评论 与其他读者分享你的观点

用户名:未登录
我的评分