Audible Noise Performance of High Voltage AC Conductor Bundles at an Altitude of 226lm
作者机构:North China Electric Power UniversityBaoding 071000China China Electric Power Research Institute(State Key Laboratory of Power Grid Environmental Protection)Wuhan 430074China
出 版 物:《CSEE Journal of Power and Energy Systems》 (中国电机工程学会电力与能源系统学报(英文))
年 卷 期:2023年第9卷第6期
页 面:2447-2455页
核心收录:
学科分类:080801[工学-电机与电器] 0808[工学-电气工程] 08[工学]
基 金:National Natural Science Foundation of China(51907065) the Fundamental Research Funds for the Central Universities(2020MS097)
主 题:AC power lines audible noise corona discharge high altitude
摘 要:Extra or ultra-high voltage transmission lines can exhibit strong corona discharge and generate severe audible noise(AN)at high altitudes,which has become a critical limiting factor for power lines ***,the AN data of bundle conductors at high altitudes are very rare,which cannot adequately support the power utilities to make reasonable conductor *** this paper,a sound pressure level(SPL)of 14 types of bundle conductors is investigated by using an ultra-high-voltage(UHV)corona cage(8 m×8 m×35 m)at an altitude of 2216 m,where the bundle numbers between 4 and 12 and the conductor types are used in 500 kV,750 kV or 1000 kV power transmission *** a large number of valuable AN data are obtained;the influences of bundle numbers and sub-conductor diameters on an acoustic power density level(LPWL)are analyzed;and an A-weighted LPWL calculation method is *** addition,by comparing the AN data obtained from the low-altitude area(altitude:23 m),the AN altitude correction factor is concluded,and the influences of conductor parameters and the surface electric field strength on correction factors are *** results obtained in this paper can provide important data for the construction of high-altitude AC power lines.