Interruption Characteristics of High-speed Switches in 500 kV Fault Current Limiter with High Coupled Split Reactance

作     者:Yanzhe Zhang Shixin Xiu Qiang Tang Shenli Jia Bo Chu Wenxiong Mo Yong Wang Haibo Su 

作者机构:State Key Laboratory of Electrical Insulation and Power Equipmentthe School of Electrical EngineeringXi'an Jiaotong UniversityXi'an 710049China. Test and Research Institute of Guangzhou Power Supply Company Ltd.Guangzhou 510410China. 

出 版 物:《CSEE Journal of Power and Energy Systems》 (中国电机工程学会电力与能源系统学报(英文))

年 卷 期:2023年第9卷第4期

页      面:1577-1584页

核心收录:

学科分类:080802[工学-电力系统及其自动化] 0808[工学-电气工程] 08[工学] 

基  金:supported by the National Key R&D Program of China(2018YFB0904300) 

主  题:Fault current limiter(FCL) high coupled split reactor(HCSR) high-speed switch interruption characteristics short circuit current. 

摘      要:A 500 kV high-voltage AC fault current limiter(FCL)based on a high coupled split reactor(HCSR)is pro-posed by the National key R&D project *** impedance under normal conditions and high impedance under short-circuit conditions are accomplished by the cooperation of HCSR and high-speed ***-speed switches play an important role in current limiting processes,thus interruption characteristics of the high-speed switch in the 500 kV FCL are studied in this *** simulation model of the FCL and the external equivalent power grid are *** short-circuit current and recovery voltage characteristics of the high-speed switch in FCL are *** results show that maximum DC component of the short-circuit current of the high-speed switch reaches 91%,the maximum peak value is 118 kA,and the longest arcing time is 14.8 *** is a discontinuity in the curve of the short-circuit current peak and arcing time as a function of the short-circuit occurrence time;the peak recovery voltage of a single break of the high-speed switch has a maximum value of 87.5 kV under a three-phase ungrounded short-circuit condition,and the rate of rise of recovery voltage is o.22 kV/*** recovery voltage peak shows a period change with the short-circuit occurrence time,and the period is 10 *** effects of the shunt capacitor value and short-circuit ground resistance on the recovery voltage of high-speed switching are also *** research can be used for reference by R&D personnel and *** Terms-Fault current limiter(FCL),high coupled split reactor(HCSR),high-speed switch,interruption characteristics,short circuit current.