咨询与建议

看过本文的还看了

相关文献

该作者的其他文献

文献详情 >Development and validation of ... 收藏

Development and validation of a transient simulation model of a full-scale PCM embedded radiant chilled ceiling

作     者:Seyedmostafa Mousavi Behzad Rismanchi Stefan Brey Lu Aye Seyedmostafa Mousavi;Behzad Rismanchi;Stefan Brey;Lu Aye

作者机构:Renewable Energy and Energy Efficiency GroupDepartment of Infrastructure EngineeringFaculty of Engineering and Information Technology(FEIT)The University of MelbourneMelbourneVIC3010Australia InvAus Pty Ltd.MelbourneVIC3000Australia 

出 版 物:《Building Simulation》 (建筑模拟(英文))

年 卷 期:2023年第16卷第6期

页      面:813-829页

核心收录:

学科分类:08[工学] 0807[工学-动力工程及工程热物理] 081404[工学-供热、供燃气、通风及空调工程] 0814[工学-土木工程] 

基  金:supported by the University of Melbourne's Research Scholarship (MRS) support of the AuScope Subsurface Observatory Program via the National Collaborative Research Infrastructure Strategy (NCRIS) 

主  题:phase change material(PCM) radiant cooling ceiling panel modelling and simulation validation 

摘      要:The recent significant rise in space cooling energy demand due to the massive use of air-conditioning systems has adversely changed buildings’energy use patterns globally.The updated energy technology perspectives highlight the need for innovative cooling systems to address this growing cooling demand.Phase change material embedded radiant chilled ceiling(PCM-RCC)has lately acquired popularity as they offer more efficient space cooling together with further demand-side flexibility.Recent advancements in PCM-RCC applications have increased the necessity for reliable simulation models to assist professionals in identifying improved designs and operating settings.In this study,a transient simulation model of PCM-RCC has been developed and validated using measured data in a full-scale test cabin equipped with newly developed PCM ceiling panels.This model,developed in the TRNSYS simulation studio,includes Type 399 that uses the Crank-Nicolson algorithm coupled with the enthalpy function to solve transient heat transfer in PCM ceiling panels.The developed model is validated in both free-running and active operation modes,and its quality is then evaluated using several validation metrics.The results obtained in multiple operating scenarios confirm that the model simulates the transient behaviour of the PCM-RCC system with an accuracy within±10%.Aided by this validated model,which offers the user detailed flexibilities in the system design and its associated operating schemas,PCM-RCC’s potentials regarding peak load shifting,energy savings,and enhanced thermal comfort can be investigated more reliably.

读者评论 与其他读者分享你的观点

用户名:未登录
我的评分