文献详情 >Dynamic thermal rating assessm... 收藏

Dynamic thermal rating assessment of oil-immersed power transformers for multiple operating conditions

作     者:Chen Zhang Xuzhu Dong Jiangjun Ruan Yongqing Deng 

作者机构:School of Electrical Engineering and AutomationWuhan UniversityWuhanHubeiChina 

出 版 物:《High Voltage》 (高电压(英文))

年 卷 期:2024年第9卷第1期

页      面:195-205页

核心收录:

学科分类:080801[工学-电机与电器] 0808[工学-电气工程] 08[工学] 

基  金:National Natural Science Foundation of China-State Grid Corporation Joint Fund for Smart Grid,Grant/Award Number:U2066217 Key Research and Development Program of Hubei Province,Grant/Award Number:2021BAA182 

主  题:load thermal power 

摘      要:In this article,the dynamic thermal rating assessment method of oil-immersed power transformer with multiple operating conditions is proposed,considering the constraints of hot spot temperature(HST),top oil temperature,losses of life and the maximum allowable current of on-load tap changer(OLTC)or bushing,which can determine the dynamic load curves under different operating conditions and give the most sensitive constraints to limit the dynamic load *** improve the accuracy of HST estimation,the temperature estimation model is also improved and the thermal parameters are optimised using the HST measured by optical ***,several application examples are studied for transformers in different *** results show that the normal cyclic dynamic transformer rating(DTR)is mainly limited by the losses of life when the ambient temperature is high,and the average load factor can be increased to 0.82 with a maximum load capacity of *** main limiting factor of short-term DTR is the OLTC or bushing current constraint,and the average load factor can be increased to *** maximum load capacity of the transformer under both operating conditions is 23%and 50%higher than its rated load capacity,indicating that the transformer still has a large load potential available.

读者评论 与其他读者分享你的观点

用户名:未登录
我的评分