咨询与建议

看过本文的还看了

相关文献

该作者的其他文献

文献详情 >Zone 3 Relay Blocking Scheme t... 收藏

Zone 3 Relay Blocking Scheme to Prevent Cascaded Events

Zone 3 Relay Blocking Scheme to Prevent Cascaded Events

作     者:LIM Seong-Il 

作者机构:Department of Electrical EngineeringKyungnam UniversityMasanKorea 

出 版 物:《Transactions of Tianjin University》 (天津大学学报(英文版))

年 卷 期:2008年第14卷第2期

页      面:97-105页

核心收录:

学科分类:080802[工学-电力系统及其自动化] 0808[工学-电气工程] 08[工学] 

基  金:Ministry of Science&Technology of Korea and Korea Science&Engineering Foundation Through ERC(Engineering Research Center)Program 

主  题:blackouts cascaded events defense system distance relay Zone 3 relay 

摘      要:Defense systems are needed to prevent catastrophic failures of a power grid due to cascaded events. Cascaded events can be attributed to improper operations of protective relays. The most challenging problem for the design and implementation of a defense system is the performance in accuracy and speed in a real time environment. Protective devices are normally designed to operate fast in order to isolate the fault(s). This paper proposes a new methodology to distinguish line overloads from actual faults for distance relays. In order to distinguish between line flow transfers from a line outage and an actual fault, the line outage distribution factor (LQDF) and generation shift factor (GSF) based power flow estimation method, and a secure peer to peer (P2P) communication structure are adopted. Computer simulations of cascaded events for a 6-bus system and the Korean power grid have been performed to establish the feasibility of the proposed scheme.

读者评论 与其他读者分享你的观点

用户名:未登录
我的评分