咨询与建议

看过本文的还看了

相关文献

该作者的其他文献

文献详情 >An Improved Algorithm of Groun... 收藏

An Improved Algorithm of Grounding Grids Corrosion Diagnosis Based on Total Least Square Method

An Improved Algorithm of Grounding Grids Corrosion Diagnosis Based on Total Least Square Method

作     者:ZHANG Ying-jiao NIU Tao WANG Sen 

作者机构:School of Electrical Engineering Xi'an Jiaotong University Xi'an 710049 China Jiangsu Electric Power Design Institute Nanjing 211102 China Shaanxi Electric Power Research Institute Xi'an 710054 China 

出 版 物:《高压电器》 (High Voltage Apparatus)

年 卷 期:2011年第47卷第5期

页      面:22-29页

学科分类:0808[工学-电气工程] 080802[工学-电力系统及其自动化] 0809[工学-电子科学与技术(可授工学、理学学位)] 08[工学] 0807[工学-动力工程及工程热物理] 

主  题:corrosion property grounding grids corrosion diagnosis ambiguous total least square touch and step voltages 

摘      要:A new model considering corrosion property for grounding grids diagnosis is proposed,which provides reference solutions of ambiguous *** constraint total least square method based on singular value decomposition is adopted to improve the effectiveness of grounding grids diagnosis *** improvement can weaken the influence of the model s error,which results from the differences between design paper and actual *** influence on touch and step voltages caused by the interior resistance of conductors is taken into *** results show the validity of this approach.

读者评论 与其他读者分享你的观点

用户名:未登录
我的评分