Study on variation of smoke component concentration with water mist applying
Study on variation of smoke component concentration with water mist applying作者机构:Communication and Information Center State Administration of Work Safety Beijing 100013 China
出 版 物:《Engineering Sciences》 (中国工程科学(英文版))
年 卷 期:2014年第12卷第3期
页 面:58-64页
基 金:National Natural Science Foundation Youth Science Foundation (No.50904041) China Postdoctoral Science Foundation (No.20070410067)
摘 要:Interaction between water mist and fire smoke is studied by experiments in an ISO 9705 room, The variation of 02, CO and CO2 concentration is disclosed, and the mathematical models of smoke component con- centration with water mist pressure and ventilation speed are established according to the experimental results. It is found in the experiment that the smoke component concentration will break when ventilation speed exceeds 1.5 kg/s. This paper provides necessary theory for water mist technology using in smoke restraining.