Influence of ageing on oil degradation and gassing tendency under high-energy electrical discharge faults for mineral oil and synthetic ester

作     者:L.Loiselle U.Mohan Rao I.Fofana 

作者机构:Research Chair on the Aging of Power Network Infrastructure(ViAHT)Universitédu QuébecàChicoutimiChicoutimiQCG7H 2B1Canada 

出 版 物:《High Voltage》 (高电压(英文))

年 卷 期:2020年第5卷第6期

页      面:731-738页

核心收录:

学科分类:0808[工学-电气工程] 080803[工学-高电压与绝缘技术] 08[工学] 

主  题:synthetic energy high 

摘      要:In this work, mineral oil and synthetic esters were selected at different ageing factors (based on acidity values). Fresh and aged oils have been subjected to high-energy discharges (repeated 100 breakdowns) to simulate electric faults of highly vulnerable intensity. The intent of this work is to understand the influence of high-energy electric faults on oil degradation and gassing tendency at different ageing conditions. In this study, the influence of the high-energy discharges on degradation and gassing tendency at different ageing factors is reported for mineral oil and synthetic esters. Oil degradation is reported by adopting ultraviolet spectroscopy, turbidity and particle counter as per american society for testing and materials (ASTM) standard test methods. Gassing tendencies and fault gas analysis are understood by dissolved the gas analysis using Duval s triangle and Duval s pentagon methods for mineral and non-mineral oils. It is found that the influence of high-energy discharges on oil degradation is higher in mineral oils to that of the synthetic esters. The intensity of the gassing tendency is higher for ester fluids;however, as per the Duval methods, the faulty conditions are at lower levels as compared to mineral oils.

读者评论 与其他读者分享你的观点

用户名:未登录
我的评分